The EP-2700 filter has a break point at 200 Hz. This is also called the cutoff frequency.
From 60 Hz to 200 Hz there is a reduction of 3 dB in the voltage distortion. This measurement describes the Magnitude of Noise.
From 60 Hz to 200 Hz the graph shows a total 3 dB reduction or 1/1.414 ratio(Ratio is the amount reduced by the dB factor).
From 60 Hz to 2 kHz the graph shows a 20 dB decrease or a factor of 10.
The 20 dB per decade total decline from 200 Hz to 20 kHz shows a 40 dB decrease or a factor of 100.
This unit will not work for a VFD; it will attenuate the control frequency.

MODEL # A D H I
MODEL TYPE 3 Phase Wye 3Phase Delta 3 Phase Wye 3 Phase Delta
CIRCUIT DESC. Internal Circuit Breaker -> Spectrum Multiplier -> Low-Pass Filter ->Dissipative Absorber(Parallel Operated)
NOM.LINE VOLTAGE 300 to 500 V 300 to 500 V 500 to 600 V 500 to 600 V
MAX CONT.LINE CURRENT N/A (Parallel Device)
CONNECTION Wire leads
PROTECTION MODES Line to Neutral Line to Neutral Line to Neutral Line to Line
FREQUENCY RESPONSE -30 dB reduction from 5 kHz to 2 MHz
SAFETY APPROVALS CSA Standards Class 9091 01 & 9091 81, UL 1283, NEMA LS-1 1992, IEC 939
SAFETY RATINGS Fire Rating 94V-O
APPLICATION ENVIRONMENT Subpanel Distribution, PLC Protection, Buss Plug, Machine Feed
SIZE & WEIGHT Dimensions:6.25 dia. x 4.50" weight:7lbs. Dimensions: 6 x 8 x 4" ht. weight:15lbs.
MATERIALS Aluminum or Plastic Housing, LED Indicator Lamps, 14 ga 600V Rated Wire.
Circuit encapsulated in epoxy to retain integrity of circuitry in failure mode.
WIRE Size: 14 ga. Length: 3`
ACCESSORIES Red LED Indicator Lights = Failure Mode
COMPLIANCE NEMA LS-1, Electrical Notice 516